Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

59

Configuring the I/O

Chapter 4

If the bridge has a different I/O configuration than the configuration now
being saved, the Online/Offline mismatch dialog box will appear.

a. When both Options choices are available, click ‘Use offline data

(download)’. When this choice is dimmed (grayed out), you must click
‘Use online data (upload)’.

b. Click OK.

9.

From the File menu, choose Save to save the I/O configuration file to the
computer.

If this is the first time you saved the project, the Save As dialog box appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.

The Save Configuration dialog box appears.

d. Click OK to download the I/O configuration to the bridge.

TIP

If a message box reports that the download cannot be completed
because the controller is not in Program mode, click Change Mode to
place the controller in Remote Program mode and continue the
download.

TIP

When both Save Type choices are available, we recommend to click
‘Optimize and re-write schedule for all connections’.