Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual
Page 71
![background image](/manuals/577801/71/background.png)
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
71
Using the I/O
Chapter 5
Figure 16 - ControlLogix Controller Example Ladder Logic Program Using a Drive Generic Profile for
Logic Command/Reference
Example Datalink Data
The Datalink data used in the example program is shown in
Figure 17
. Note that
to describe the parameters to which the Datalinks are assigned, you may want to
add descriptions to the automatically-created generic controller tags or create a
UDDT. For this example, the DL_From_Net tags were created to describe the
drive parameters to which these Datalinks are assigned. For example,
DL_From_Net _01_Stop_Mode_A indicates that option module
Host
Parameter 01 - [DL From Net 01]
is assigned to drive parameter 370 - [Stop
Mode A]. This same method applies to the DL_To_Net tags.