Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 102

Advertising
background image

102

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Appendix B

Option Module Parameters

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

[DL To Net 01]
[DL To Net 02]
[DL To Net 03]
[DL To Net 04]
[DL To Net 05]
[DL To Net 06]
[DL To Net 07]
[DL To Net 08]
[DL To Net 09]
[DL To Net 10]
[DL To Net 11]
[DL To Net 12]
[DL To Net 13]
[DL To Net 14]
[DL To Net 15]
[DL To Net 16]
Sets the port number and parameter number to which the
selected Datalinks should connect. Each selected port/parameter
will be read and their values transmitted over the network to the
controller. These are parameters read by the controller (inputs to
the controller).

If setting the value manually, the parameter value = (10000 *
port number) + (origination parameter number). For example,
suppose you want to use Host Parameter 17 - [DL To Net 01] to
read Parameter 02 of an optional I/O module plugged into drive
Port 6. The value for Host Parameter 17 - [DL To Net 01] would
be 60002 [(10000 * 6) + 2].

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

159999

Type:

Read/Write

Reset Required:

No

33

[Comm Flt Action]
Sets the action that the option module and drive will take if the
option module detects that I/O communication has been
disrupted. This setting is effective only if I/O that controls the
drive is transmitted through the option module. When
communication is re-established, the drive will automatically
receive commands over the network again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

Parameter

No.

Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. Host
Parameter 33 - [Comm Flt Action] lets you determine the action of
the option module and connected drive if I/O communication is
disrupted. By default, this parameter faults the drive. You may configure
this parameter so that the drive continues to run, however, precautions
should be taken to verify that the setting of this parameter does not
create a risk of injury or equipment damage. When commissioning the
drive, verify that your system responds correctly to various situations (for
example, a disconnected cable).