Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

95

Troubleshooting

Chapter 7

13

DPI Baud 125kbps

The option module detected that the drive was communicating at 125 Kbps.

14

DPI Baud 500kbps

The option module detected that the drive was communicating at 500 Kbps.

15

DPI Host Invalid

The option module was connected to an incompatible product.

16

DPI Dup Port

Another peripheral with the same port number is already in use.

17

DPI Type 0 Logon

The option module has logged in for Type 0 control.

18

DPI Type 0 Time

The option module has not received a Type 0 status message within the specified time.

19

DPI DL Logon

The option module has logged into a Datalink.

20

DPI DL Error

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.

21

DPI DL Time

The option module has not received a Datalink message within the specified time.

22

DPI Ctrl Disable

The option module has sent a ‘Soft Control Disable’ command to the drive.

23

DPI Ctrl Enable

The option module has sent a ‘Soft Control Enable’ command to the drive.

24

DPI Msg Timeout

A Client-Server message sent by the option module was not completed within 1 second.

25

DPI Manual Reset

The option module was reset by changing its Reset Module parameter.

SI Events

26

SI Online

The option module has logged into the Serial Interface Communication.

27

SI Logon Error

The option module failed to log into the Serial Interface.

28

SI Comm Fault

The Serial Interface Communication has faulted.

Network Events

29

Net Link Up

A network link was available for the option module.

30

Net Link Down

The network link was removed from the option module.

31

Net Dup Address

The option module uses the same address as another device on the network.

32

Net Comm Fault

The option module detected a communication fault on the network.

33

Net Sent Reset

The option module received a reset from the network.

34

Net IO Close

An I/O connection from the network to the option module was closed.

35

Net Idle Fault

The option module received ‘idle’ packets from the network.

36

Net IO Open

An I/O connection from the network to the option module has been opened.

37

Net IO Timeout

An I/O connection from the network to the option module has timed out.

38

Net IO Size Err

The option module received an incorrectly sized I/O packet.

39

PCCC IO Close

The device sending PCCC Control messages to the option module has set the PCCC Control Timeout to zero.

40

PCCC IO Open

The option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).

41

PCCC IO Timeout

The option module has not received a PCCC Control message for longer than the PCCC Control Timeout.

42

Msg Ctrl Open

The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing control messages
to be sent to the option module.

43

Msg Ctrl Close

The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control messages to
be sent to the option module.

44

Msg Ctrl Timeout

The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.

45-57

Reserved

58

Module Defaulted

The option module has been set to defaults.

Table 12 - Option Module Events (Continued)

Code

Event Text

Description

Advertising