Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

101

Option Module Parameters

Appendix B

Host Parameters

07

[Reset Module]
No action if set to ‘0’ (Ready). Resets the option module if set to
‘1’ (Reset Module). Restores the option module to its factory
default settings if set to ‘2’ (Set Defaults). This parameter is a
command. It will be reset to ‘0’ (Ready) after the command has
been performed.

When performing a Set Defaults, the drive may detect a conflict.
If this occurs, the drive will not allow a Set Defaults action. You
must resolve the conflict before attempting a Set Defaults action
for the option module.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:

No

Parameter

No.

Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. If the option
module is transmitting I/O that controls the drive, the drive may fault
when you reset the option module. Determine how your drive will
respond before resetting the option module.

Parameter

No.

Name and Description

Details

01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16

[DL From Net 01]
[DL From Net 02]
[DL From Net 03]
[DL From Net 04]
[DL From Net 05]
[DL From Net 06]
[DL From Net 07]
[DL From Net 08]
[DL From Net 09]
[DL From Net 10]
[DL From Net 11]
[DL From Net 12]
[DL From Net 13]
[DL From Net 14]
[DL From Net 15]
[DL From Net 16]
Sets the port number and parameter number to which the
selected Datalinks should connect. Each selected port/parameter
will be written with data received from the network. These are
parameters written by the controller (outputs from the
controller).

If setting the value manually, the parameter value = (10000 *
port number) + (destination parameter number). For example,
suppose you want to use Host Parameter 01 - [DL From Net
01]
to write to Parameter 01 of an optional encoder module
plugged into drive Port 5. The value for Host Parameter 01 - [DL
From Net 01]
would be 50001 [(10000 * 5) + 1].

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

159999

Type:

Read/Write

Reset Required:

No