Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

55

Configuring the I/O

Chapter 4

Figure 9 - Output Image Controller Tags

Save the I/O Configuration to the Controller

After adding the bridge and drive/option module to the I/O configuration, you
must download the configuration to the controller. You should also save the
configuration to a file on your computer.

1.

From the Communications menu in the RSLogix 5000 dialog box, choose
Download.

The Download dialog box appears.

TIP

When using RSLogix 5000 software, version 16.00 or later, you can add the I/O
configuration of a Generic Profile while the controller is online and in the Run
mode.

TIP

If a message box reports that RSLogix 5000 software is unable to go
online, find your controller in the Who Active dialog box. From the
Communications menu, choose Who Active. After finding and
selecting the controller, click Set Project Path to establish the path. If
your controller does not appear, you need to add or configure the
ControlNet driver with RSLinx software. See

Using RSLinx Classic

Software on page 35

and RSLinx online help for details.