Chapter 2

Installing the Option Module

Setting the Node Address
Switches

Set the option module Node Address switches (

Figure 1

) by rotating the switches

to the desired value for each digit.

Figure 1 - Setting Node Address Switches

The switch settings can be verified by viewing

Device Parameter 06 - [Net Addr

Act]

or Diagnostic Device Item number 58 (

page 93

) with any of the following

drive configuration tools:

PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM

Connected Components Workbench software, version 1.02 or later

DriveExplorer software, version 6.01 or later

DriveExecutive software, version 5.01 or later

IMPORTANT

Each node on the ControlNet network must have a unique address. Set the
node address before power is applied because the option module uses the
node address it detects when it first receives power. To change a node address,
you must set the new value and then remove and reapply power to (or reset)
the option module.

Settings

Description

00

If the Node Address switches are set to ‘00’, the option module uses the value stored in Device Parameter
05 - [Net Addr Cfg]
for the node address. See

Setting the Node Address on page 26

.

01…99

Node address used by the option module. The default switch setting is 02.

0

5

4

9

3

8

2

7

1

6

0

5

4

9

3

8

2

7

1

6

0

5

4

9

3

8

2

7

1

6

0

5

4

9

3

8

2

7

1

6

ONES

Position

TENS

Position