N-files – Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 111

Advertising
background image

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

111

ControlNet Objects

Appendix C

N-Files

N-File

Description

N42

This N-file lets you read and write some values configuring the port.

N42:3

Time-out (read/write): Time (in seconds) allowed between messages to the N45 file. If the option
module does not receive a message in the specified time, it performs the fault action configured in its
[Comm Flt Action] parameter. A valid setting is between 1 and 32767 seconds (5…20 seconds is
recommended).

N42:7

Option Module Port Number (read only): Drive port in which the drive resides.

N42:8

Peer Option Modules (read only): Bit field of devices having peer messaging capabilities.

N45

This N-file lets you read and write control I/O messages. You can write control I/O messages only when
all of the following conditions are true:

The option module is not receiving I/O from a scanner. For example, there is no scanner on the

network, the scanner is in idle (program) mode, the scanner is faulted, or the option module is not
mapped to the scanner.

The option module is configured to receive I/O (for example, the [DLs From Net 01-16] parameter).

The value of N42:3 is set to a non-zero value.

Write

Read

N45:0
N45:1
N45:2
N45:3
N45:4
N45:5
N45:6
N45:7
N45:8
N45:9
N45:10
N45:11
N45:12
N45:13
N45:14
N45:15
N45:16
N45:17
N45:18
N45:19
N45:20
N45:21
N45:22
N45:23
N45:24
N45:25
N45:26
N45:27
N45:28
N45:29
N45:30
N45:31
N45:32
N45:33
N45:34
N45:35

Logic Command (least significant)
Logic Command (most significant)
Reference (least significant)
Reference (most significant)
DL From Net 01 (least significant)
DL From Net 01 (most significant)
DL From Net 02 (least significant)
DL From Net 02 (most significant)
DL From Net 03 (least significant)
DL From Net 03 (most significant)
DL From Net 04 (least significant)
DL From Net 04 (most significant)
DL From Net 05 (least significant)
DL From Net 05 (most significant)
DL From Net 06 (least significant)
DL From Net 06 (most significant)
DL From Net 07 (least significant)
DL From Net 07 (most significant)
DL From Net 08 (least significant)
DL From Net 08 (most significant)
DL From Net 09 (least significant)
DL From Net 09 (most significant)
DL From Net 10 (least significant)
DL From Net 10 (most significant)
DL From Net 11 (least significant)
DL From Net 11 (most significant)
DL From Net 12 (least significant)
DL From Net 12 (most significant)
DL From Net 13 (least significant)
DL From Net 13 (most significant)
DL From Net 14 (least significant)
DL From Net 14 (most significant)
DL From Net 15 (least significant)
DL From Net 15 (most significant)
DL From Net 16 (least significant)
DL From Net 16 (most significant)

Logic Status (least significant)
Logic Status (most significant)
Feedback (least significant)
Feedback (most significant)
DL To Net 01 (least significant)
DL To Net 01 (most significant)
DL To Net 02 (least significant)
DL To Net 02 (most significant)
DL To Net 03 (least significant)
DL To Net 03 (most significant)
DL To Net 04 (least significant)
DL To Net 04 (most significant)
DL To Net 05 (least significant)
DL To Net 05 (most significant)
DL To Net 06 (least significant)
DL To Net 06 (most significant)
DL To Net 07 (least significant)
DL To Net 07 (most significant)
DL To Net 08 (least significant)
DL To Net 08 (most significant)
DL To Net 09 (least significant)
DL To Net 09 (most significant)
DL To Net 10 (least significant)
DL To Net 10 (most significant)
DL To Net 11 (least significant)
DL To Net 11 (most significant)
DL To Net 12 (least significant)
DL To Net 12 (most significant)
DL To Net 13 (least significant)
DL To Net 13 (most significant)
DL To Net 14 (least significant)
DL To Net 14 (most significant)
DL To Net 15 (least significant)
DL To Net 15 (most significant)
DL To Net 16 (least significant)
DL To Net 16 (most significant)

Advertising