Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 104

Advertising
background image

104

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

Appendix B

Option Module Parameters

38

[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if any of the
following is true:

Host Parameter 33 - [Comm Flt Action] is set to ‘4’ (Send

Flt Cfg) and I/O communication is disrupted.

Host Parameter 34 - [Idle Flt Action] is set to ‘4’ (Send Flt

Cfg) and the controller is idle.

Host Parameter 36 - [Msg Flt Action] is set to ‘4’ (Send Flt

Cfg) and explicit messaging for drive control is disrupted.

Default:

0

Minimum:

-3.40282 x 10

38

Maximum:

3.40282 x 10

38

Type:

Read/Write

Reset Required:

No

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54

[Flt Cfg DL 01]
[Flt Cfg DL 02]
[Flt Cfg DL 03]
[Flt Cfg DL 04]
[Flt Cfg DL 05]
[Flt Cfg DL 06]
[Flt Cfg DL 07]
[Flt Cfg DL 08]
[Flt Cfg DL 09]
[Flt Cfg DL 10]
[Flt Cfg DL 11]
[Flt Cfg DL 12]
[Flt Cfg DL 13]
[Flt Cfg DL 14]
[Flt Cfg DL 15]
[Flt Cfg DL 16]
Sets the data that is sent to the Datalink in the drive if any of the
following is true:

Host Parameter 33 - [Comm Flt Action] is set to ‘4’ (Send

Flt Cfg) and I/O communication is disrupted.

Host Parameter 34 - [Idle Flt Action] is set to ‘4’ (Send Flt

Cfg) and the controller is idle.

Host Parameter 36 - [Msg Flt Action] is set to ‘4’ (Send Flt

Cfg) and explicit messaging for drive control is disrupted.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required:

No

Parameter

No.

Name and Description

Details