Communication fault protection, Underload warning, Comm fault warning – Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 15

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

Protection Functions 2-5

Underload Warning

The following parameters are available for configuring the DeviceNet
Module's underload warning performance:

• Parameter 22, UL Inhibit Time, allows the installer to inhibit an

underload indication from occurring during the motor starting
sequence. It is adjustable from 0…250 seconds.

• Parameter 23, UL Warn Level, allows the installer to define the current at

which the DeviceNet Module will indicate a warning. It is
user-adjustable from 30…100% of the FLA dial setting.

The DeviceNet Module will immediately indicate an Underload warning if:

• No warning currently exists
Underload Warning is enabled
UL Inhibit Time has expired
• The motor current is less than the UL Warn Level

When the Underload Warning conditions are satisfied, the following will
occur:

• Bit 3 in Parameter 4, Warning Status, will go to “1”
• Bit 1 of Parameter 10, Device Status, will go to “1”

Communication Fault
Protection

A disruption of the communication link between the E1 Plus DeviceNet
Module and a DeviceNet network can result in the loss of application control
and/or critical process diagnostic data. Rapid communication fault detection
helps minimize potential damage due to uncontrolled or unmonitored
applications.

Comm Fault Warning

The DeviceNet Module will indicate a Comm Fault warning if:

• No warning currently exists
• Comm Fault Warning is enabled
• The DeviceNet Module experiences a loss of communication

IMPORTANT

The Underload Warning function does not include a time
delay feature. Once the UL Inhibit Time has expired, the
Underload warning indication is instantaneous.