Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 37

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

Device Parameters 4-13

OutA DN IdlState

Parameter No. 38

This parameter, in conjunction with
parameter 39, defines how Output A will
respond when the DeviceNet network is idle.
When set to “1”, Output A will hold the state
prior to trip occurrence. When set to “0”,
Output A will open or close as determined by
the setting in Parameter 39. The DN Flt
parameters supersede the DN Idl
parameters.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Go To IdlValue (#39)

Max. Value

1 = Hold Last State

Default Value

0

OutA DN IdlValue

Parameter No. 39

This parameter determines the state that Output
A assumes when the network is idle and
parameter 38 is set to “0”.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = Closed

Default Value

0

IN1 Assignment

Parameter No. 40

This parameter allows the user to assign a
specific function to the discrete IN1 input.

Access Rule

Get/Set

Data Type

USINT

Group

I/O Setup

Units

Min. Value

Max. Value

0 = Normal
1 = Trip reset
2 = OL Contact

Default Value

0

IN2 Assignment

Parameter No. 41

This parameter allows the user to assign a
specific function to the discrete IN2 inputs.

Access Rule

Get/Set

Data Type

USINT

Group

I/O Setup

Units

Min. Value

Max Value

0 = Normal
1 = Trip Reset
2 = OL Contact

Default Value

0