Publication 193-UM006A-EN-P – October 2005

3-4 DeviceNet Node Commissioning

8. Next to the selected Polled check box, do the following:

• Type 6 in Input Size.
• Type 1 in Output Size.

9. Select

Next. RSNetWorx uploads the EDS file from the E1 Plus

DeviceNet Module.

10. To display the icon options for the node, select

Next.

11. Select the E1 Plus Overload Relay icon by highlighting it and clicking

Change Icon.

12. After selecting the desired icon, select

OK.

13. Select

Next.

14. When prompted to register this device, select

Next.

15. Select

Finish. After a short time, RSNetWorx updates the online screen

by replacing “Unrecognized Device” with the name and icon given by
the EDS file that you have just registered.

Using the Node Commissioning Tool of RSNetWorx for DeviceNet

1. From the Tools menu at the top of the screen, select

Node

Commissioning.

2. Select

Browse.

Figure 3.4 Node Commissioning Device Solution Window