Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 27

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

Device Parameters 4-3

Trip Status

Parameter No. 3

This parameter provides trip identification.

1 = Trip
0 = No Trip

Access Rule

Get

Data Type

WORD

Group

Monitor

Units

Min. Value

Max. Value

Default Value

None

Bit

Function:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Overload

X

Phase Loss

X

Jam

X

X

X

X

X

X

X

X

X

X

X

X

X

Not Used

Warning Status

Parameter No. 4

This parameter provides warning identification

1 = Warning
0 = No Warning

Access Rule

Get

Data Type

WORD

Group

Monitor

Units

Min. Value

Max. Value

Default Value

None

Bit

Function:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Overload

X

Not Used

X

Jam

X

Underload

X

Not Used

X

Comm Fault

X

Comm Idle

X

Nonvolatile Memory Fault

X

X

X

X

X

X

X

X

Not Used