Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 63

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

DeviceNet Information B-11

A single instance is implemented and contains the following attributes:

The following common services are implemented for the Discrete Output
Point Object:

Table B.27 Discrete Output Point Object Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Value

BOOL

0=OFF
1=ON

5

Get/Set

Fault Action

BOOL

0=Fault Value
Attribute
1=Hold Last
State

6

Get/Set

Fault Value

BOOL

0=Off
1=ON

7

Get/Set

Idle Action

BOOL

0=Fault Value
Attribute
1=Hold Last
State

8

Get/Set

Idle Value

BOOL

0=OFF
1=ON

113

Get/Set

Pr Fault Action

BOOL

0=Pr Fault Value
Attribute
1=Ignore

114

Get/Set

Pr Fault Value

BOOL

0=Off
1=On

Table B.28 Discrete Output Object Common Services

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single