Publication 193-UM006A-EN-P – October 2005

DeviceNet Information B-5

Input Assemblies

Table B.13 Instance 50 — Basic Overload Input Assembly from ODVA Overload
Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Tripped

Table B.14 Instance 51 —Extended Overload Input Assembly from ODVA Overload
Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Warning

Tripped

Table B.15 Instance 100 — Parameter Based Input Assembly

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

0

Value of the parameter pointed to by parameter #30 (low byte)

1

Value of the parameter pointed to by parameter #30 (high byte)

1

2

Value of the parameter pointed to by parameter #31 (low byte)

3

Value of the parameter pointed to by parameter #31 (high byte)

2

4

Value of the parameter pointed to by parameter #32 (low byte)

5

Value of the parameter pointed to by parameter #32 (high byte)

3

6

Value of the parameter pointed to by parameter #33 (low byte)

7

Value of the parameter pointed to by parameter #33 (high byte)

Table B.16 Instance 106 —Motor Starter Input Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Motor
Current

Input 2

Input 1

Out A Stat Warning

Tripped

Table B.17 Instance 110 —Extended Motor Starter Input Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Motor
Current

Input 2

Input 1

Out A Stat Warning

Tripped

1

Unused

2

Average %FLA

3

4

%Therm Utilized

5