Chapter
3
DeviceNet Node Commissioning
Using RSNetWorx for
DeviceNet
Going Online
To begin the configuration of an E1 Plus DeviceNet Module, execute the
RSNetWorx software and complete the following procedure. You must use
RSNetWorx Revision 3.21 Service Pack 2 or later.
1. After going on-line using RSNetWorx for DeviceNet, do the following:
• Select the Network menu.
• Select Online.
2. Choose the appropriate DeviceNet PC interface. In this example, a
1784-PCD module is chosen. Other common DeviceNet interfaces are
the 1770-KFD and 1784-PCIDS.
Note: DeviceNet drivers must be configured using RSLinx prior to being
available to RSNetWorx.
3. Select OK.
4. RSNetWorx notifies the user to upload or download devices before
viewing configuration. Select OK.
5. RSNetWorx now browses the network and displays all of the nodes it
has detected on the network. For some versions of RSNetWorx
software, the E1 Plus DeviceNet Module EDS files may not be
included, and the device will be identified as an “Unrecognized Device”.
If the screen appears like the following example, continue with
Building and Registering an EDS file.