Publication 193-UM006A-EN-P – October 2005

4-12 Device Parameters

I/O Setup Group

OutA Pr FltState

Parameter No. 34

This parameter, in conjunction with
parameter 35, defines how Output A will
respond when a trip occurs. When set to “1”,
Output A will continue to operate as
commanded via the network. When set to
“0”, Output A will open or close as
determined by the setting of parameter 35.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Go To FltValue (#35)

Max. Value

1 = Ignore Fault

Default Value

0

OutA Pr FltValue

Parameter No. 35

This parameter determines the state that Output
A assumes when a trip occurs and Parameter 34
is set to “0”.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = closed

Default Value

0

OutA DN FltState

Parameter No. 36

This parameter, in conjunction with
Parameter 37, defines how Output A will
respond when a DeviceNet network fault
occurs. When set to “1”, Output A will hold
the state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting of Parameter 37.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Go To FltValue (#37)

Max. Value

1 = Hold Last State

Default Value

0

OutA DN FltValue

Parameter No. 37

THis parameter determines the state that
Output A assumes when a DeviceNet network
fault occurs and Parameter 36 is set to “0”.

Access Rule

Get/Set

Data Type

BOOL

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = Closed

Default Value

0