Publication 193-UM006A-EN-P – October 2005
Installation and Wiring 1-5
Wiring
Figure 1.5 Wiring Diagram
ATTENTION
When using 4-conductor DeviceNet media cable (without a
shield), it is recommended that the “Shield” terminal be
wired to earth ground.
Table 1.1 Wire and Size Torque Specifications
1X
2X
24…12 AWG
24…16 AWG
5 lb.-in
1X
2X
0.2…2.5 mm
2
0.25…1 mm
2
0.55 N•m
1X
2X
0.2…2.5 mm
2
0.2…1 mm
2
0.55 N•m
DNET 24V+ (Red)
DNET 24V- (Black)
SSV
IN2
IN1
OUTA
(B300)
CAN H (White)
SHIELD
CAN L (Blue)
13
14
1
23
Advertising