Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 66

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

B-14 DeviceNet Information

The following common services are implemented for the Parameter Group
Object:

Control Supervisor Object — CLASS CODE 0x0029

No class attributes are supported for the Control Supervisor Object. A single
instance (instance 1) of the Control Supervisor Object is supported. The
following instance attributes are supported.

Table B.34 Parameter Group Object Common Services

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

Table B.35 Control Supervisor Object Instance Attributes

Attribute
ID

Access Rule

Name

Data Type

Value

10

Get

Tripped

BOOL

0=No Fault present
1= Fault Latched

11

Get

Warning

BOOL

0=No Warning Present
1=Warning present (not latched)

12

Get/Set

Fault Reset

BOOL

1…>1=Trip Reset; otherwise no action

13

Get

Trip Code

UINT

ODVA TRip Code—In trip state indicates cause of trip; if not tripped,
indicates cause of last trip.

14

Get

Warning Code

UINT

ODVA Warning Code—In warning state indicates cause of warning;
if no warning, indicates cause of last warning.

100

Get

Trip Status

WORD

Bit 0=Overload
Bit 1=Phase Loss
Bit 2=Jam
Bit 3=Not Used
Bit 4=Not Used
BIt 5=Not Used
Bit 6=Not Used
Bit 7=Not Used

101

Get

Warning Status

WORD

Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7=EEPROM

102

Get

Trip Lob 0

WORD

Last trip condition. Bit definitions of the value are the same as
attribute 114.

103

Get

Trip Log 1

WORD

Last trip condition. Bit definitions of the value are the same as
attribute 114.