Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 31

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

Device Parameters 4-7

OL Reset Mode

Parameter No. 16

This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment
while the DeviceNet Module is powered. Note,
however, that the E1 Plus manual reset button,
accessible at the front, is always active.

Access Rule

Get/Set

Data Type

BOOL

Group

Advanced Setup

Units

Min. Value

0 = Manual

Max. Value

1 = Automatic

Default Value

0

OL Warning Level

Parameter No. 17

This parameter sets the overload warning level.

Access Rule

Get/Set

Data Type

USINT

Group

Advanced Setup

Units

% Thermal
Utilization

Min. Value

0

Max. Value

100

Default Value

90

Jam Inhibit Time

Parameter No. 18

This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.

Access Rule

Get/Set

Data Type

USINT

Group

Advanced Setup

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10

Jam Trip Delay

Parameter No. 19

This parameter allows the installer to program a
time duration for which a jam condition must
exist at the programmed level prior to the device
tripping.

Access Rule

Get/Set

Data Type

USINT

Group

Advanced Setup

Units

Seconds

Min. Value

0.5

Max. Value

25.0

Default Value

5.0