Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual
Page 31

Publication 193-UM006A-EN-P – October 2005
Device Parameters 4-7
OL Reset Mode
Parameter No. 16
This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment
while the DeviceNet Module is powered. Note,
however, that the E1 Plus manual reset button,
accessible at the front, is always active.
Access Rule
Get/Set
Data Type
BOOL
Group
Advanced Setup
Units
—
Min. Value
0 = Manual
Max. Value
1 = Automatic
Default Value
0
OL Warning Level
Parameter No. 17
This parameter sets the overload warning level.
Access Rule
Get/Set
Data Type
USINT
Group
Advanced Setup
Units
% Thermal
Utilization
Min. Value
0
Max. Value
100
Default Value
90
Jam Inhibit Time
Parameter No. 18
This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.
Access Rule
Get/Set
Data Type
USINT
Group
Advanced Setup
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10
Jam Trip Delay
Parameter No. 19
This parameter allows the installer to program a
time duration for which a jam condition must
exist at the programmed level prior to the device
tripping.
Access Rule
Get/Set
Data Type
USINT
Group
Advanced Setup
Units
Seconds
Min. Value
0.5
Max. Value
25.0
Default Value
5.0