Publication 193-UM006A-EN-P – October 2005
Specifications A-3
RF Immunity
Test Level
Performance Criteria
10V/m
1①✍
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
2 kV (Power)
1 kV (control)
1①✍
Surge Immunity
Test Level
Performance Criteria
2 kV L-E
1 kV L-L
1①✍
Radiated Emissions
Class A
Conducted Emissions
Not tested
①
Performance Criteria 1 requires the DUT (device under test) not to experience degradation or loss of
performance.
✍
Environment 2 - Heavy Industrial.
WARNING
This is a class A product. In domestic environment, this product may cause radio interference, in which case the
user may be required to take adequate measures.
DeviceNet Communications:
Baud Rate
125 k, 250 k, 500 k
Auto-Baud Rate identification
Yes
Group 2 - Master-Slave Connection Set
Yes
Polled I/O Messaging
Yes
Change of State Messaging
Yes
Cyclic Messaging
Yes
Explicit Messaging
Yes
Full Parameter Object Support
Yes
Group 4 - Off-line Node Recovery Messaging
Yes
Configuration Consistency Value
Yes
Unconnected Message Manager (UCMM)
Yes
Jam Protection:
Trip Level
150…600% FLA
Trip Delay
0.1…25.0 sec.
Inhibit
0…250 sec.
Standards
UL 508
CSA 22.2, No. 14
EN 60947-4-1