Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 70

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

B-18 DeviceNet Information

A single instance (instance 1) of the DeviceNet Interface Object is supported:

The following common services are implemented for the DeviceNet Interface
Object.

Table B.42 Acknowledge Handler Object Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Min/Max

Default

Description

5

Get/Set

Nonvolatile MAC ID

USINT

0…63

63

6

Get/Set

Nonvolatile Baud

USINT

0…2

0

7

Get/Set

Assy Word 0 Param

USINT

0…41

1

8

Get/Set

Assy Word 1 Param

USINT

0…41

2

9

Get/Set

Assy Word 2 Param

USINT

0…41

3

10

Get/Set

Assy Word 3 Param

USINT

0…41

4

12

Get

Firmware Rev

UINT

0…65.535

1.001

Firmware rev in EDS
parameter format

15

Get/Set

Autobaud Enable

BOOL

0…1

1

1=Enabled
0=Disabled

16

Get/Set

Consumed Assy

USINT

0…103

103

Output Assembly Instance

17

Get/Set

Produced Assy

USINT

0…110

110

Input Assembly Instance

18

Get/Set

Param Lock

BOOL

0…1

0

0=Unlocked
1=Locked

19

Get/Set

Set To Defaults

BOOL

0…1

0

0=No action
1=Reset

Table B.43 DeviceNet Interface Object Common Services

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single