Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 56

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

B-4 DeviceNet Information

The following services are implemented for the DeviceNet Object:

Assembly Object — CLASS CODE 0x0004

The following class attributes are supported for the Assembly Object:

Output Assemblies

The following output assembly instances are implemented:

Table B.8 DeviceNet Object Common Services

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Allocate_Master/Slave_Connection_Set

0x4C

No

Yes

Release_Master/Slave_Conncetion _Set

Table B.9 Assembly Object Class Attributes

Attribute ID

Access Rule

Name

Data Type

Value

2

Get

Max Instance

UINT

TBD

Table B.10 Instance 2 — Basic Overload Output Assembly from ODVA Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Trip Reset

Table B.11 Instance 101 — Similar to Basic Contactor Output Assembly in ODVA
Contactor Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Output A

Table B.12 Instance 103 — Similar to Basic Motor Starter Output Assembly in
ODVA Starter Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Trip Reset

Output A

Advertising