B-4 DeviceNet Information
The following services are implemented for the DeviceNet Object:
Assembly Object — CLASS CODE 0x0004
The following class attributes are supported for the Assembly Object:
Output Assemblies
The following output assembly instances are implemented:
Table B.8 DeviceNet Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave_Connection_Set
0x4C
No
Yes
Release_Master/Slave_Conncetion _Set
Table B.9 Assembly Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
2
Get
Max Instance
UINT
TBD
Table B.10 Instance 2 — Basic Overload Output Assembly from ODVA Profile
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Trip Reset
Table B.11 Instance 101 — Similar to Basic Contactor Output Assembly in ODVA
Contactor Profile
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Output A
Table B.12 Instance 103 — Similar to Basic Motor Starter Output Assembly in
ODVA Starter Profile
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Trip Reset
Output A