Publication 193-UM006A-EN-P – October 2005

4-2 Device Parameters

Parameter Group Listing

The 193-EDN DeviceNet Module contains six parameter groups

Monitor Group

Table 4.1 Parameter Groups

Monitor
parameters

Advanced Setup

Reset/Lock

DeviceNet Setup

I/O Setup

Trip History

1 Average %FLA

12 Trip Enable

14 Trip Reset

26 AutoBaudEnable

34 OutA Pr FltState

5 Trip Log 0

2%Therm Utilized

13 Warning Enable

24 Program Lock

27 NonVol Baud Rate

35 OutA Pr FltValue

6 Trip Log 1

3 Trip Status

15 Single/Three Ph

25 Set to Defaults

28 Output Assembly

36 OutA DN FltState

7 Trip Log 2

4 Warning Status

16 OL Reset Mode

29 Input Assembly

37 OutA DN FltValue 8 Trip Log 3

10 Device Status

17 OL Warning Level

30 Prod Assy Word 0

38 OutA DN IdlState

9 Trip Log 4

11 Firmware

18 Jam Inhibit Time

31 Prod Assy Word 1

39 OutA DN IdlValue

19 Jam Trip Delay

32 Prod Assy Word 2

40 IN1 Assignment

20 Jam Trip Level

33 Prod Assy Word 3

41 IN2 Assignment

21 Jam Warn Level

22 UL Inhibit Time

23 UL Warn Level

Average %FLA

Parameter No. 1

This parameter reports the average motor current.
The value is reported as a percentage of motor rated
current (dial setting on the E1 Plus Overload Relay),
and is reported in increments of 5.

Access Rule

Get

Data Type

UINT

Group

Monitor

Units

%FLA

Min. Value

0

Max. Value

1275

Default Value

None

% Therm Utilized

Parameter No. 2

This parameter reports the percent thermal
utilization of the connected motor.

Access Rule

Get

Data Type

USINT

Group

Monitor

Units

%

Min. Value

0

Max. Value

100

Default Value

None