Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 59

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

DeviceNet Information B-7

Connection Object — CLASS CODE 0x0005

No class attributes are supported for the Connection Object. Multiple
instances of the Connection Object are supported, instances 2 and 4 from the
group 2 predefined master/slave connection set, and instances 5-7 are
available explicit UCMM connections.

Instance 2 is the Polled I/O Message Connection. The following instance 2
attributes are supported:

Table B.19 Connection Object Instance 2 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=Nonexistant
1= Configuring
3=Established
4=Timed out

2

Get

Instance Type

USINT

1=I/O Connection

3

Get

Transport Class Trigger

USINT

0x82: Server, Transport Class 2
(If alloc_choice!=polled and ack suppression
is enabled, the value = 0x80)

4

Get

Produced Connection ID

UINT

01111xxxxxx
xxxxxx=node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101
xxxxxx=node address

6

Get

Initial Comm Characteristics

USINT

0x21

7

Get

Produced Connection Size

UINT

0…8

8

Get

Consumed Connection Size

UINT

0…8

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get/Set

Watchdog Action

USINT

0=Transition to timed out
1=Auto deleted
2=Auto reset

13

Get

Produced Connection Path Length

UINT

8

14

Get/Set

Produced Connection Path

21 04 00 25 (assy inst) 00 30 03

15

Get

Consumed Connection Path Length

UINT

8

16

Get/Set

Consumed Connection Path

21 04 00 25 (assy inst) 00 30 03