Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual
Page 32
Publication 193-UM006A-EN-P – October 2005
4-8 Device Parameters
Jam Trip Level
Parameter No. 20
This parameter sets the jam trip level.
Access Rule
Get/Set
Data Type
UINT
Group
Advanced Setup
Units
% FLA
Min. Value
150
Max. Value
600
Default Value
250
Jam Warn Level
Parameter No. 21
This parameter sets the jam warning level.
Access Rule
Get/Set
Data Type
UINT
Group
Advanced Setup
Units
% FLA
Min. Value
100
Max. Value
600
Default Value
150
UL Inhibit Time
Parameter No. 22
This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.
Access Rule
Get/Set
Data Type
USINT
Group
Advanced Setup
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10
UL Warn Level
Parameter No. 23
This parameter sets the underload warning
level.
Access Rule
Get/Set
Data Type
USINT
Group
Advanced Setup
Units
% FLA
Min. Value
30
Max. Value
100
Default Value
70