4-8 Device Parameters

Jam Trip Level

Parameter No. 20

This parameter sets the jam trip level.

Access Rule

Get/Set

Data Type

UINT

Group

Advanced Setup

Units

% FLA

Min. Value

150

Max. Value

600

Default Value

250

Jam Warn Level

Parameter No. 21

This parameter sets the jam warning level.

Access Rule

Get/Set

Data Type

UINT

Group

Advanced Setup

Units

% FLA

Min. Value

100

Max. Value

600

Default Value

150

UL Inhibit Time

Parameter No. 22

This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.

Access Rule

Get/Set

Data Type

USINT

Group

Advanced Setup

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10

UL Warn Level

Parameter No. 23

This parameter sets the underload warning
level.

Access Rule

Get/Set

Data Type

USINT

Group

Advanced Setup

Units

% FLA

Min. Value

30

Max. Value

100

Default Value

70