Overload object —class code 0x002c, Devicenet interface object — class code 0x00b4 – Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 69

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

DeviceNet Information B-17

6.12. Overload Object —CLASS CODE 0x002C

No class attributes are supported for the Overload Object. A single instance
(instance 1) of the Overload Object is supported:

The following common services are implemented for the Overload Object:

DeviceNet Interface Object — CLASS CODE 0x00B4

The following class attributes are supported for the DeviceNet Interface
Object:

Table B.39 Overload Object Instance Attributes

Attribute ID

Access Rule Name

Data Type

Value

7

Get

% Thermal Utilized

USINT

xxx% FLA

108

Get

Average %FLA

UINT

0…1000 %FLA

109

Get

% Thermal Utilized

USINT

0…100%

127

Get/Set

Single/Three Phase

BOOL

0=Single Phase
1=Three Phase

132

Get/Set

OL Warn Level

USINT

0…100% TCU

141

Get/Set

Jam Inhibit Time

USINT

0…250 Sec.

142

Get/Set

Jam Trip Delay

USINT

0.5…25.0 Sec.

143

Get/Set

Jam Trip Level

UINT

150…600 %FLA

144

Get/Set

Jam Warn Level

UINT

100…600 %FLA

145

Get/Set

UL Inhibit Time

USINT

0…250 Sec.

148

Get/Set

UL Warn Level

USINT

30…100 %FLA

Table B.40 Overload Object Common Services

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table B.41 DeviceNet Interface Object Class Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

3

Advertising