Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual

Page 61

Advertising
background image

Publication 193-UM006A-EN-P – October 2005

DeviceNet Information B-9

Instances 5…7 are available group 3 Explicit Message Connections that are
allocated through the UCMM. The following attributes are supported:

The following are implemented for the Connection Object:

Table B.21 Connection Object Instances 5…7 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=Nonexistant
1=Configuring
3=Established
4=Timed out

2

Get

Instance Type

USINT

0=Explicit Message

3

Get

Transport Class Trigger

USINT

0x83: Server, Transport Class 3

4

Get

Produced Connection ID

UINT

Depends on message group and Message ID

5

Get

Consumed Connection ID

UINT

Depends on message group and Message ID

6

Get

Initial Comm Characteristics

USINT

0x33 (Group 3)

7

Get

Produced Connection Size

UINT

0

8

Get Consumed

Connection

Size

UINT

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get

Watchdog Action

USINT

01=auto delete
03=deferred delete

13

Get

Produced Connection Path Length

UINT

0

14

Get

Produced Connection Path

Empty

15

Get

Consumed Connection Path Length

UINT

0

16

Get

Consumed Connection Path

Empty

Table B.22 Connection Object Common Services

Service Code

Implemented for:

Service Name

Class

Instance

0x05

No

Yes

Reset

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Advertising