Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual
Page 61

Publication 193-UM006A-EN-P – October 2005
DeviceNet Information B-9
Instances 5…7 are available group 3 Explicit Message Connections that are
allocated through the UCMM. The following attributes are supported:
The following are implemented for the Connection Object:
Table B.21 Connection Object Instances 5…7 Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0=Nonexistant
1=Configuring
3=Established
4=Timed out
2
Get
Instance Type
USINT
0=Explicit Message
3
Get
Transport Class Trigger
USINT
0x83: Server, Transport Class 3
4
Get
Produced Connection ID
UINT
Depends on message group and Message ID
5
Get
Consumed Connection ID
UINT
Depends on message group and Message ID
6
Get
Initial Comm Characteristics
USINT
0x33 (Group 3)
7
Get
Produced Connection Size
UINT
0
8
Get Consumed
Connection
Size
UINT
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
01=auto delete
03=deferred delete
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
Empty
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Empty
Table B.22 Connection Object Common Services
Service Code
Implemented for:
Service Name
Class
Instance
0x05
No
Yes
Reset
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single