Publication 193-UM006A-EN-P – October 2005
A-2 Specifications
Recommended Control Circuit Fuse
KTK-R-6
(6 A, 600V)
Rated Number of Operations
Out A:
W/100-C-09…100-C43
W/100-C-60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3
5,000,000
2,500,000
1,000,000
300,000
Input Ratings:
Terminals
IN 1:
IN 2:
SSV (Sensor Supply Voltage)
1
2
3
Supply Voltage (provided by module)
24V DC±15%
Type of Inputs
Current Sinking
ON-State Voltage
15V DC
On-State Current (turn-on)
2 mA
Steady State Current
5 mA
Off-State Voltage
5V DC
Off-State Current
0.5 mA
Transition Voltage
5…15V DC
Transition Current
0.5…2.0 mA
Environmental Ratings:
Ambient Temperature Tamb
Storage
Operating
(Open)
(Enclosed)
-40…+85°C (-40…+185°F)
-20…+60°C (-4…+140°F)
-20…+40°C (-4…+104°F)
Humidity
Operating
Damp Heat - Steady State
Damp Heat - Cyclic
5…95% non-condensing
per IEC 68-2-3
per IEC 68-2-30
Cooling Method
Natural Convection
Vibration (per IEC 68-2-6)
3 G
Shock (per IEC 68-2-27)
30 G
Maximum Altitude
2000 m
Pollution Environment
Pollution Degree 2
Terminal Marking
EN 50012
Degree of Protection
IP20
Electromagnetic Compatibility
Electrostatic Discharge Immunity
Test Level
Performance Criteria
8 kV Air Discharge
4 kV Contact Discharge