Mount the cn2dn device on a din rail – Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual
Page 10

10 ControlNet-to-DeviceNet Linking Device
Publication
1788-IN052D-EN-P - February 2007
Mount the CN2DN Device on a DIN Rail
Complete the following steps to mount the CN2DN device on a DIN
rail.
1. Align the CN2DN device over the DIN rail.
2. Press the CN2DN device onto the DIN rail until the DIN rail
latches lock the linking device in place.
ATTENTION
This product is grounded through the DIN rail to chassis ground. Use
zinc plated yellow-chromate steel DIN rail to assure proper grounding.
The use of other DIN rail materials (for example, aluminum and
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting
surface approximately every 200 mm (7.87 in.) and use end-anchors
appropriately.
IMPORTANT
The DIN rail must be properly grounded. See publication Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
for more information about DIN rail grounding.
Press Forward
and Down