Environmental Specifications

Attribute

Value

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80
MHz

EFT/B Immunity

IEC 61000-4-4:
±4 kV at 2.5 kHz on power ports
±2 kV at 5 kHz on communications ports

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 KHz sine-wave 80% AM from 30...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing

Shock, Non-Operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Shock, Operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Surge Transient Immunity

IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports