The address of the device is already
in use by another device on the
network. The scanner failed the
duplicate node address check.

Change the address of the device
to an unused address.

71

Invalid data in scan list.

Use RSNetworx software to
reconfigure the scan list.

72

Slave device stopped communicating.
If the slave device does not recover
communication during next scan,
status code changes to 78.

• Verify slave device’s:

power.

communication

connections.

• If slave device is polled, verify

that interscan delay time is
adequate for the device to
return data.

73

Slave device’s identity information
does not match electronic key in
scanner.

• Make sure that the correct

device is connected at this
address.

• Make sure that the device

matches the specified
electronic key (vendor,
product code, product type).

74

Scanner detected data overrun on
DeviceNet communication port.

• Modify your configuration

and check for invalid data.

• Check network

communication traffic.

DeviceNet Status Codes

Status Code Description of Status

Recommended Action