5. If need to troubleshoot Status Register tags, use the following

table as a reference to interpret module or network status.

Status Register Tag Values

If Tag Member

Displays
Value

Then Status Is

Run

0

Scanner in idle mode.

Run

1

Scanner in run mode.

Fault

0

Scanner not faulted.

Fault

1

Scanner faulted.

DisableNetwork

0

Scanner not disabled.

DisableNetwork

1

Scanner disabled.

DeviceFailure

0

Scanner communicating with all devices.

DeviceFailure

1

Scanner not communicating with at least 1 device.

AutoVerify

0

Data size of each device matches the amount of
memory allocated for the device in the scanner.

AutoVerify

1

Data size of at least 1 device does not match the
amount of memory allocated for the device in the
scanner.

CommFailure

0

No network-wide communication problem exists

CommFailure

1

Network-wide communication problem exists

DupNodeFail

0

Scanner is on the network at a unique address

DupNodeFail

1

Scanner is trying to get on the network at an
address that is already in use.

DnetPowerDetect

0

Network connector of the scanner has power.

DnetPowerDetect

1

Network connector of the scanner does not have
power.