5. If need to troubleshoot Status Register tags, use the following
table as a reference to interpret module or network status.
Status Register Tag Values
If Tag Member
Displays
Value
Then Status Is
Run
0
Scanner in idle mode.
Run
1
Scanner in run mode.
Fault
0
Scanner not faulted.
Fault
1
Scanner faulted.
DisableNetwork
0
Scanner not disabled.
DisableNetwork
1
Scanner disabled.
DeviceFailure
0
Scanner communicating with all devices.
DeviceFailure
1
Scanner not communicating with at least 1 device.
AutoVerify
0
Data size of each device matches the amount of
memory allocated for the device in the scanner.
AutoVerify
1
Data size of at least 1 device does not match the
amount of memory allocated for the device in the
scanner.
CommFailure
0
No network-wide communication problem exists
CommFailure
1
Network-wide communication problem exists
DupNodeFail
0
Scanner is on the network at a unique address
DupNodeFail
1
Scanner is trying to get on the network at an
address that is already in use.
DnetPowerDetect
0
Network connector of the scanner has power.
DnetPowerDetect
1
Network connector of the scanner does not have
power.