ControlNet-to-DeviceNet Linking Device 35

Publication

1788-IN052D-EN-P - February 2007

86

The device is in idle mode, or not
producing data, while the scanner is
in run mode.

• Check the configuration and

status of the device.

• If you set up an interlock

between 2 scanners
(controllers), make sure both
scanners are in run mode.

87

Scanner cannot listen to shared
inputs from slave device because the
owning scanner has not established
communication with that slave
device.

• Verify primary scanner

connection and configuration.

• Slave device may not be

producing data.

88

Scanner cannot listen to shared
inputs from slave device because I/O
parameters (for example, polled or
strobed, electronic key, data size) for
that slave device are configured
differently between this scanner and
the owning scanner.

In this scanner, reconfigure the I/O
parameters for the shared inputs
scan list entry so that they match
those same parameters in the
owning scanner.

89

Scanner failed to configure a device
using the Automatic Device Recovery
(ADR) parameters.

• Make sure that you installed

a compatible device.

• If the offline configuration of

the device does not match the
actual (online) configuration
of the device, change the
offline configuration to match
the online configuration.

90

Controller has set the scanner to the
disabled mode.

If desired, turn enable the scanner
by locating the
O.CommandRegister.DisableNetw
ork bit of the command register
and turn if off.

DeviceNet Status Codes

Status Code Description of Status

Recommended Action