Linking activity status – Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 24

Advertising
background image

24 ControlNet-to-DeviceNet Linking Device

Publication

1788-IN052D-EN-P - February 2007

Linking Activity Status

The Linking Activity LED indicator displays the status of
communication between the DeviceNet and ControlNet networks as
well as the amount of traffic.

Use the following table to interpret the Linking Activity LED indicator.

Linking Activity LED Indicator

LED Indicator

Linking Activity Status

Off

No network traffic is occurring between the ControlNet to
DeviceNet networks. I/O traffic may be present.

Green, flashing

ControlNet to DeviceNet (non-I/O) communication traffic
present (flash rate indicates amount of traffic).

Red and Green, flashing

Module is running boot code only (used for FLASH upgrades).

Advertising