24 ControlNet-to-DeviceNet Linking Device
Publication
1788-IN052D-EN-P - February 2007
Linking Activity Status
The Linking Activity LED indicator displays the status of
communication between the DeviceNet and ControlNet networks as
well as the amount of traffic.
Use the following table to interpret the Linking Activity LED indicator.
Linking Activity LED Indicator
LED Indicator
Linking Activity Status
Off
No network traffic is occurring between the ControlNet to
DeviceNet networks. I/O traffic may be present.
Green, flashing
ControlNet to DeviceNet (non-I/O) communication traffic
present (flash rate indicates amount of traffic).
Red and Green, flashing
Module is running boot code only (used for FLASH upgrades).