Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 33

Advertising
background image

ControlNet-to-DeviceNet Linking Device 33

Publication

1788-IN052D-EN-P - February 2007

80

Scanner is in idle mode.

If desired, put network in run
mode by completing the following
steps.

1. Put the controller in run or

remote run mode using the
keyswitch on the controller or
through RSLogix5000
software.

2. Turn on the bit

O.CommandRegister.Run for
the scanner.

81

Controller has set the scanner to the
faulted mode. The Command bit also
indicates a DeviceNet network fault
state.

Bit O.CommandRegister.Fault for
the scanner is on. Correct
condition that caused controller to
set this bit and then turn this bit
off.

82

Error detected in sequence of
fragmented I/O messages from
device.

Use RSNetWorx software to:

check scan list of the

device to make sure that
its input and output data
sizes are correct.

check the configuration of

the device.

DeviceNet Status Codes

Status Code Description of Status

Recommended Action