32 ControlNet-to-DeviceNet Linking Device

Publication

1788-IN052D-EN-P - February 2007

78

Device is configured in scan list, but
not communicating. It has failed to
communicate during the scanner’s
second scan, which followed the
display of status error code 72.

• Verify device’s:

power.

communication

connections.

• If the device is polled, make

sure the interscan delay is
long enough for the device to
return its data.

• If needed, use RSNetWorx

software to:

add the device to the

DeviceNet network.

delete the device from

scanner’s scan list.

inhibit the device in the

scanner’s scan list.

79

Scanner has failed to transmit a
message. The error status usually
displays after the duplicate node
check completes at power-up.

• Make sure that your scanner

is connected to a valid
network.

• Check for disconnected

cables.

• Verify network baud rate.

DeviceNet Status Codes

Status Code Description of Status

Recommended Action