Devicenet network status – Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 26

Advertising
background image

26 ControlNet-to-DeviceNet Linking Device

Publication

1788-IN052D-EN-P - February 2007

DeviceNet Network Status

The DeviceNet network indicators, DNet Network Status and DNet
I/O Status, indicate the state of the DeviceNet network and the state
of DeviceNet I/O modules.

Use the following tables to interpret your DeviceNet LED indicators
located at the top right corner of the CN2DN device.

DNet Network Status Indicator

LED Indicator

DeviceNet Network
Status

Recommended Action

Off

No DeviceNet connection.

If a DeviceNet connection has been
made:

A. Verify that the DeviceNet

network is powered.

B. Check DeviceNet cables and

connections.

Green, flashing

DeviceNet network found,
not communicating with
devices.

If devices should be communicating:

A. Check DeviceNet cables and

connections.

B. Verify that all devices on the

DeviceNet network are
functioning properly.

Advertising