Bus-off condition likely due to cable
or signal errors.
• Cycle power to the device.
• Verify that all devices are set
to the same baud rate.
• Check DeviceNet cabling to
make sure no short circuits
exist between CAN (blue and
white) wires and power or
shield (black, red, and shield)
wires.
• Check the media system for
the following noise sources:
– Device located near
high-volt power cable.
– Incorrect or no termination
resistor used.
– Improper grounding.
– Device on network
producing noise or
incorrect data for the
network.
92
DeviceNet cable not supplying power
to the device’s communication port.
• Verify the network’s 24V dc
power supply is operating
properly.
• Verify good cable condition.
• Check cable connections to
the device.
95
A device’s firmware is being updated
or a configuration is being
downloaded.
None. Do not disconnect the
device while the update is in
process as existing data in device
memory will be lost.