Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 36

Advertising
background image

36 ControlNet-to-DeviceNet Linking Device

Publication

1788-IN052D-EN-P - February 2007

91

Bus-off condition likely due to cable
or signal errors.

• Cycle power to the device.
• Verify that all devices are set

to the same baud rate.

• Check DeviceNet cabling to

make sure no short circuits
exist between CAN (blue and
white) wires and power or
shield (black, red, and shield)
wires.

• Check the media system for

the following noise sources:

Device located near

high-volt power cable.

Incorrect or no termination

resistor used.

Improper grounding.

Device on network

producing noise or
incorrect data for the
network.

92

DeviceNet cable not supplying power
to the device’s communication port.

• Verify the network’s 24V dc

power supply is operating
properly.

• Verify good cable condition.
• Check cable connections to

the device.

95

A device’s firmware is being updated
or a configuration is being
downloaded.

None. Do not disconnect the
device while the update is in
process as existing data in device
memory will be lost.

DeviceNet Status Codes

Status Code Description of Status

Recommended Action