European hazardous location approval – Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 4

Advertising
background image

4 ControlNet-to-DeviceNet Linking Device

Publication

1788-IN052D-EN-P - February 2007

European Hazardous Location Approval

European Zone 2 Certification (The following applies when the
product bears the EEx Marking)

This equipment is intended for use in potentially explosive
atmospheres as defined by European Union Directive 94/9/EC.

The LCIE (Laboratoire Central des Industries Electriques) certifies that
this equipment has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of
Category 3 equipment intended for use in potentially explosive
atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has
been assured by compliance with EN 60079-15.

IMPORTANT

This equipment is not resistant to sunlight or other sources of UV
radiation.

Equipment of lesser Enclosure Type Rating must be installed in an
enclosure providing at least IP54 protection when applied in Class
I, Zone 2 environments.

This equipment shall be used within its specified ratings defined by
Allen-Bradley.

Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when
applied in Class I, Zone 2 environments.

Advertising