ControlNet-to-DeviceNet Linking Device 27

Publication

1788-IN052D-EN-P - February 2007

Green, steady

One or more devices
connected and
communicating.

None needed.

Red, flashing

One or more connections
timed-out.

Use programming software to view
tags specific to the devices in order
to troubleshoot the DeviceNet
network.

See DeviceNet Modules in
Logix5000 Control Systems,
publication DNET-UM004, for more
information about using controller
tags to troubleshoot connection
errors.

Red, steady

Communication error (bus
off condition).

A. Verify that each device has be

assigned a unique node
address.

B. Verify that specified DeviceNet

baud rates are the same.

C. Cycle power to the CN2DN

device.

See DeviceNet Modules in
Logix5000 Control Systems,
publication DNET-UM004, for more
information about using controller
tags to troubleshoot connection
errors.

DNet Network Status Indicator

LED Indicator

DeviceNet Network
Status

Recommended Action