Wire a Power Supply to the CN2DN Device
The CN2DN device requires 18...30V dc input power provided by a
power supply that is separate from the DeviceNet network power
supply.
Complete the following steps to wire the power supply to the CN2DN
linking device.
1. Disconnect power to the power supply.
2. Locate the orange power connector.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), power to this
equipment and DeviceNet must be powered from a source compliant
with the following: Safety Extra Low Voltage (SELV) or Protected Extra
Low Voltage (PELV).
To comply with UL restrictions, DeviceNet must be powered from a
source compliant with the following: Class 2 or Limited
Voltage/Current.
ATTENTION
24V dc power connection wiring length must be less than 10 m (32.81
ft).
+ -
Power Connector, Top
Power Connector
+ - + -
Power Supply
Wiring
Terminals
Daisy Chain
to Device
Wiring
Terminals
(Optional Use)