Wire a Power Supply to the CN2DN Device

The CN2DN device requires 18...30V dc input power provided by a
power supply that is separate from the DeviceNet network power
supply.

Complete the following steps to wire the power supply to the CN2DN
linking device.

1. Disconnect power to the power supply.

2. Locate the orange power connector.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), power to this
equipment and DeviceNet must be powered from a source compliant
with the following: Safety Extra Low Voltage (SELV) or Protected Extra
Low Voltage (PELV).

To comply with UL restrictions, DeviceNet must be powered from a
source compliant with the following: Class 2 or Limited
Voltage/Current.

ATTENTION

24V dc power connection wiring length must be less than 10 m (32.81
ft).

+ -

Power Connector, Top

Power Connector

+ - + -

Power Supply

Wiring

Terminals

Daisy Chain

to Device

Wiring

Terminals

(Optional Use)