Controlnet network status – Rockwell Automation 1788-CN2DN ControlNet-to-DeviceNet Linking Device Installation Instructions User Manual

Page 25

Advertising
background image

ControlNet-to-DeviceNet Linking Device 25

Publication

1788-IN052D-EN-P - February 2007

ControlNet Network Status

The CNet A and CNet B LED indicators display the status of the
ControlNet network and individual channels.

The ControlNet network may recognize more than one network
status a time. If more than one status is present, the CN2DN linking
device will display the highest priority status.

Use the following table to interpret the ControlNet LED indicators.

ControlNet LED Indicators, CNet A and CNet B

LED Indicator State

LED View

Priority
Level

ControlNet Network Status

Off

Both CNet A
and CNet B

1
(highest
priority)

No power.

Red, steady

Both CNet A
and CNet B

2

No ControlNet network found.

Red and green,
alternating

Both CNet A
and CNet B

3

Device self-testing.

Red, alternating

Both CNet A
and CNet B

4

Incorrect ControlNet node
configuration.

Off

One, CNet A
or CNet B

5

ControlNet channel disabled or not
supported.

Red and green, flashing

One, CNet A
or CNet B

6

Incorrect ControlNet network
configuration.

Red, flashing

One, CNet A
or CNet B

7

No data received from network.

Green, flashing

One, CNet A
or CNet B

8

Temporary channel error or
listen-only channel.

Green, steady

One, CNet A
or CNet B

9
(lowest)

Normal network operation.