ControlNet-to-DeviceNet Linking Device 23

Publication

1788-IN052D-EN-P - February 2007

Green, flashing

The CN2DN device is
functioning but not
communicating with
devices.

Use RSNetworx software to configure the
CN2DN device. See Additional Resources
for publications with more information
about configuring the CN2DN device.

Green, steady

Fully operational. The
CN2DN device is
communicating with
all configured
DeviceNet nodes or
there are no
configured devices.

None. The device has passed self-tests and
is functioning properly if devices have been
configured.

Red, flashing

The linking device is
not communicating
with one or more
modules.

A. Verify that DeviceNet switches are not

set at PGM.

B. Verify that connected devices are

functioning properly.

C. Verify that devices have been

configured properly.

See Additional Resources for publications
with more information about configuring
the CN2DN device.

Red, steady

Unrecoverable
communication fault.

A. Verify that the CN2DN device has been

assigned a unique node address during
configuration.

B. Verify that all devices are set at the

same baud rate.

C. Cycle CN2DN power.

D. Replace the CN2DN device.

Module Status Indicator

LED Indicator

Device Status

Recommended Action