100 Input, Output, Status and Configuration Files for Analog Modules when used with ControlNet

The I/O map for a module is divided into read words and write
words. Read words consist of input and status words, and write words
consist of output and configuration words. The number of read words
or write words can be 0 or more. The length of each I/O module’s
read words and write words vary in size depending on module
complexity. Each I/O module will support at least 1 input word or 1
output word. Status and configuration are optional, depending on the
module.

For example, a 16 point discrete input module will have up to 2 read
words and 1 write word.

Polled I/O Structure

Output data is received by the adapter in the order of the installed I/O
modules. The Output data for Slot 0 is received first, followed by the
Output data for Slot 1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter Status
Word. This is followed by the input data from each slot, in the order
of the installed I/O modules. The Input data from Slot 0 is first after
the status word, followed by Input data from Slot 2, and so on up to
slot 7.

Module Image

Inputs

Delay

Time

Input Size

Output Size

1 or 2 Words

0 or 1 Word

I/O Image

Not used

16-point Discrete Input Module

Delay

Time

Not used

Adapter Status

Slot 0 Input Data

Slot 1 Input Data

Slot 7 Input Data

Slot 0 Output Data

Slot 1 Output Data

Slot 7 Output Data

Read Data

Write Data

Network READ

Network WRITE

DeviceNet Adapter

Slot 0

I/O Module

Read

Write

Slot 1

I/O Module

Slot 7

I/O Module

...

...

...

...

...