Communication and I/O Image Table Mapping with the DeviceNet/ControlNet Adapter 91

Isolated Analog Combo Module (Cat. No. 1794-IF2XOF2I Series B)
Image Table Mapping

Module Image

I/O Image

Input Data Channel 0

Input Data Channel 1

Read Back Output Data Channel 0

Read Back Output Data Channel 1

Output Data Channel 0

Output Data Channel 1

Input Size

Output Size

0 to 7 Words

0 to 7 Words

Read

Write

Real Time Sample

PU FP CF

BD DN

V1 V0

U1 U0

W1 W0

P1 P0

Set to 0

EN S1 S0

Channel Configuration

Real Time Sample Programmed Interval

IC

RV QK CK GO

Channel #

1

Channel Filters

Q0

Q1

TR IT

Table 5.11

Analog Combo Module (1794-IF2XOF2I) Read

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 0

Input Data Channel 0

Word 1

Input Data Channel 1

Word 2

Read Back Output Channel 0

Word 3

Read Back Output Channel 1

Word 4

0

Real Time Sample

Word 5

PU

FP

CF

0

Reserved

0

0

0

0

0

BD

DN

0

Word 6

0

0

0

0

P1

P0

0

0

0

0

V1

V0

W1

W0

U1

U0

Where:
PU = Power up unconfigured state
FP = Field power off
CF = In configuration mode
BD = Calibration bad
DN = Calibration accepted

P0 and P1 = Output holding in response to Q0 thru Q1
W0 and W1 = Wire off current loop status for input channels 0 and 1
respectively. (Not used on voltage outputs.)
U0 and U1 = Underrange for input channels o and 1 respectively.
V0 and V1 = Overrange for input channels o and 1 respectively.

Advertising