Publication 1794-6.5.8 - January 2010

How to Install Your Analog Module 25

4. If daisy chaining the +24V dc power to the next base unit,

connect a jumper from terminal 51 on this base unit to terminal
34 on the next base unit. Connect the 24V dc common/return
from terminal 33 on this base unit to terminal 16 on the next
base unit.

ATTENTION

Remove field-side power before removing or
inserting the module. This module is designed so
you can remove and insert it under backplane
power. When you remove or insert a module with
field-side power applied, an electrical arc may occur.
An electrical arc can cause personal injury or
property damage by:

sending an erroneous signal to your system’s field
devices causing unintended machine motion

causing an explosion in a hazardous environment

Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating
connector. Worn contacts may create electrical
resistance.

1794-TB3, -TB3T

0 ±15

34±51

16±33

A

B

C

Row A
Row B
Row C

Row A

Row B

Row C

1794-TB3S, -TB3TS