Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 71

Advertising
background image

Publication 1794-6.5.8 - January 2010

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 71

1

0

1

0

0–10V

binary

0% Under, 2%
Over

0000–F9C2>

0000–63938>

2.5ms

2.5ms

1

0

1

1

0–5V

binary

0% Under, 4%
Over

0000–F3CF>

0000–62415>

2.5ms

2.5ms

1

1

0

0

±20mA

offset binary, 8000H =
0mA

4% Under, 4%
Over

<0618–F9E8>

<1560–63976>

2.5ms

2.5ms

1

1

0

1

4–20mA

offset binary, 8000H =
4mA

4% Under, 4%
Over

<8000–F878>

<32768–63608> 7.5ms

5.0ms

1

1

1

0

±10V

offset binary, 8000H =
0V

2% Under, 2%
Over

<031F–FCE1>

<799–64737>

2.5ms

2.5ms

1

1

1

1

±5V

offset binary, 8000H =
0V

4% Under, 4%
Over

<0618–F9E8>

<1560–63976>

2.5ms

2.5ms

(1)

Underrange for 4-20mA occurs in the blind area below 0 (3.2mA).

(2)

< and > indicate the overrun beyond actual range (about 5%).

Table 4.15

Configuring Your Input Channels

Table 4.16

Setting the Input Filter

Bits

Channel

03

02

01

00

Input Channel 0

07

06

05

04

Input Channel 1

A/D Conversion
Rate

Low Pass Filter

0

0

0

0

1200Hz

No low pass

0

0

0

1

1200Hz

100ms low pass

0

0

1

0

1200Hz

500ms low pass

0

0

1

1

1200Hz

1000ms low pass

0

1

0

0

600Hz

No low pass

0

1

0

1

600Hz

100ms low pass

0

1

1

0

600Hz

500ms low pass

0

1

1

1

600Hz

1000ms low pass

1

0

0

0

300Hz

No low pass

1

0

0

1

300Hz

100ms low pass

1

0

1

0

300Hz

500ms low pass

1

0

1

1

300Hz

1000ms low pass

1

1

0

0

150Hz

No low pass

1

1

0

1

150Hz

100ms low pass

1

1

1

0

150Hz

500ms low pass

1

1

1

1

150Hz

1000ms low pass