8 input analog module (cat. no. 1794-if4i) – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 58

Advertising
background image

Publication 1794-6.5.8 - January 2010

58 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

8 Input Analog Module (Cat. No. 1794-IF4I)

Module Image

I/O Image

Input Data Channel 0

Input Data Channel 1

Input Data Channel 2

Input Data Channel 3

Input Size

Output Size

0 to 5 Words

1 to 7 Words

Real Time Sample

PU FP CF

BD DN

Underrange

Overrange

Channel Filters

Channel Configuration

Real Time Sample Programmed Interval

IC

RV QK CK GO

Channel #

Set to 0

EN

1

TR

IT

Table 4.3

Analog Input Module (1794-IF4I) Read

Word/Dec. Bit

15

14

13 12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15 14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 0

Analog Value Channel 0

Word 1

Analog Value Channel 1

Word 2

Analog Value Channel 2

Word 3

Analog Value Channel 3

Word 4

Real Time Sample

Word 5

PU

FP

CF 0

Reserved

0

0

0

0

0

BD

DN

0

Word 6

0

0

0

0

0

0

0

0

V3

V2

V1

V0

U3

U2

U1

U0

Where:
PU = Power up unconfigured state
FP = Field power off
CF = In configuration mode
BD = Calibration bad
DN = Calibration accepted
U = Under range for specified channel
V = Overrange for specified channel

Advertising