Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 80

Advertising
background image

Publication 1794-6.5.8 - January 2010

80 Communication and I/O Image Table Mapping with the DeviceNet/ControlNet Adapter

Table 5.2

Analog Input Module (1794-IF4ICFXT) Write

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Word 0

EN

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Word 1

Channel 3 Filter

Channel 2 Filter

Channel 1 Filter

Channel 0 Filter

Word 2

Ch 3 Configuration

Ch 2 Configuration

Ch 1 Configuration

Ch 0 Configuration

Word 3

0

Real Time Sample Interval

Word 4

IC

1

TR

IT

0

CH

SK

FS

RV

QK

CK

GO

Channel Number

Word 5

Reserved

Where :

EN = Enable bit (not used on input module)

IC = Initiate Configuration bit

TR = Transparent bit

IT = Interrupt toggle bit

CH - Chop Mode Disable — use to disable the chop mode. Chop mode used by the module to reduce offset and drift errors. The
default is chop mode enabled (0).

SK = FIR Filter Disable — use to disable the FIR filter. The Finite Impulse Response filter is used by the module to improve signal
stability. The default is FIR filter enabled (0).

FS = Fast Step Response — use to enable a fast step response algorithm. The fast step response algorithm, upon sensing a step
input, uses an averaging method rather than the FIR filter. The FIR goes back into operation once the input has settled. The
default is fast step response disabled (0).

RV = Revert to default bit

QK = Quick calibration

CK = Calibration clock

GO = Gain Offset select

Table 5.3

Analog Input Module (1794-IF4I) Write Configuration Block

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

EN

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Word 2

Chnl 3 Filter

Chnl 2 Filter

Chnl 1 Filter

Chnl 0 Filter

Word 3

Chnl 3 Configuration

Chnl 2 Configuration

Chnl 1 Configuration

Chnl 0 Configuration

Word 4

0

Real Time Sample Programmed Interval

Word 5

IC

1

TR

IT

0

0

0

0

RV

QK

CK

GO

Channel Number

Word 6

Not used

Word 7

Not used

Word 7

Not used

Where:
EN = Not used on the 1794-IF4I.
IC = Initiate configuration bit
TR = Transparent bit
IT = Interrupt Toggle bit
RV = Revert to defaults bit
QK = Quick calibration
CK = Calibration clock
GO = Gain offset select

Advertising